Due to the overflow of the 10-bit counter, some devices will "go back in time" by 1024 weeks (almost 20 years). This will occur on the night of September 17-18. The problem will affect - and this is now a sure thing - Microsemi's (AKA Symmetricom) SyncServer (100, 200 and 300 series), TimeProvider 1000, parts of TimeProvider 5000 and Timesource TS3x00 (and a few others), which are popular in industrial networks.

Loss of historical data and event logs, logging and security problems, loss of process visualization - these are some of the surprises that can happen when, having received the wrong date, other devices also decide to "time travel."
What to do?
If your network is running one of the aforementioned devices, it's best to disconnect it in advance. Unfortunately, most of them are no longer supported by the manufacturer and no patches are expected. So it looks like they will become quite useless after September 17.
This leaves very little time, therefore, to replace them with new solutions. If you are not sure whether the problem also affects your device, you can unplug it on September seventeenth, and if it shows the correct date the next day, plug it in again. Of course, such a maneuver is possible only in those networks that can operate without time synchronization according to GPS for several/some hours.

Comments (75) 15 threads

Show all comments

Showing thread 1 of 15

fanf21 reply#
This is not the GPS week counter rollover https://en.m.wikipedia.org/wiki/GPS_week_number_rollover

But instead it is a device-specific rollover. It’s relatively common for GPS receivers to handle the limited week counter by having a baked-in epoch that is more recent than the latest rollover, which gives them a nearly 20 year lifetime after that epoch instead of failing at the GPS rollover.

8organicbits3 replies#
If I'm following, the thought is: It's currently Sept 17th 2002, our counter will roll over in 2019 (17 years). But since we know 1999-2001 has already past, we can hard code logic to add 20 years to any counter that's reporting that range. That updated logic rolls over on Sept 17th 2022, which buys us three extra years. This works for devices that will EOL within 20 years.

I think devices that need a longer life should keep track of the last seen timestamp, then they can detect a rollover. The device would keep a local rollover counter and just add 20 years per count. This should stay correct until that counter rolls over, or if the device is offline for >20 years.

bathtub3652 replies#
The epoch is the date & time that the minimum value of that field refers to. For Unix derived or inspired machines it’s typically the Unix epoch of 00:00:00 on January 1, 1970. This means that a timestamp of “0” refers to that date and time, and increases at whatever granularity a timestamp value maps to. If you bake the epoch into the device at the factory as being the date of manufacture and your timestamp value has 20 years worth of granularity then you get a 20 year life from manufacture time before the timestamp rolls over to 0 again.

If you’re going to use more space keep a rollover counter you may as well just add more bits to your timestamp field instead, since every bit doubles the amount of time that field can represent.

mlyle#
> If you’re going to use more space keep a rollover counter you may as well just add more bits to your timestamp field instead, since every bit doubles the amount of time that field can represent.

The GPS week counter is part of the signal GPS satellites send and is not easily changed by the manufacturer of receivers.
Of course, devices that accept CNAV now have a few extra bits to work with.

mlyle#
> I think devices that need a longer life should keep track of the last seen timestamp, then they can detect a rollover. The device would keep a local rollover counter and just add 20 years per count. This should stay correct until that counter rolls over, or if the device is offline for >20 years.

Better in some ways, worse in others.
Can still result in unexpected behavior if configuration memory is lost.
And if it ever accepts an invalid future time for whatever reason, it gets "stuck" in that failure state.

hedora#
It is easier than that. You can use unsigned integer wraparound.

Truncate the current wall clock time to a 10 bit unsigned, then subtract the number reported by the device, and interpret the result as an unsigned 10 bit. That's the amount of time that has passed since the device emitted its timestamp. (Assuming at most one wraparound event.)