Console is flickering between "website is unavailable" and being up for my team. This is happening very frequently just now, reliability seems to have taken a hit.

Comments (614) 80 threads

Show all comments

Showing thread 1 of 80

aledalgrande7 replies#
If you haven't seen yet, news is it was a power loss:

> 5:01 AM PST We can confirm a loss of power within a single data center within a single Availability Zone (USE1-AZ4) in the US-EAST-1 Region. This is affecting availability and connectivity to EC2 instances that are part of the affected data center within the affected Availability Zone. We are also experiencing elevated RunInstance API error rates for launches within the affected Availability Zone. Connectivity and power to other data centers within the affected Availability Zone, or other Availability Zones within the US-EAST-1 Region are not affected by this issue, but we would recommend failing away from the affected Availability Zone (USE1-AZ4) if you are able to do so. We continue to work to address the issue and restore power within the affected data center.

codeduck1 reply#
another example of a single dc in a single AZ rendering an entire region almost unusable. This has shades of eu-central-1 all over again.
nightpool4 replies#
Amazon is claiming the failure is limited to a single AZ. Are you seeing failures for instances outside of that AZ? If not, how has this rendered "the entire region almost unusable"?
londons_explore3 replies#
A lot of people will automatically fail over jobs to other AZ's. That often involves spinning up lots more EC2 instances and moving PB's of data. The end result is all capacity on other AZ's gets used up, and networks get full to capacity, and even if those other zones are technically working, practically they aren't really usable.

Continue this thread — 3 replies

tyingq#
Perspective, I would guess. Unless you spend a lot of time on retry/timeout/fail logic around AWS apis, your app could be stuck/blocked in the RunInstances() api, for example.
matharmin2 replies#
Yes, I've seen issues that affected the entire region. In my specific case, I happened to have an ElastiCache cluster in the affected AZ that became unreachable (my fault for single AZ). But even now, I'm unable to create any new ElastiCache clusters in different AZs (which I wanted to use for manual failover). And there were a lot of errors on the AWS console during the outage.

"almost unusable" is maybe exaggerating, but there were definitely issues affecting more than just the single AZ.

Continue this thread — 2 replies

codeduck4 replies#
We've had alerts for packet loss and had issues in recovering region-spanning services (both AWS and 3rd party).

Yes, some of these we should be better at handling ourselves, but... it's all very well to say "expect to lose an AZ" but during this outage it's not been physically possible to remove the broken AZ instances from multi-AZ services because we cannot physically get them to respond to or acknowledge commands.
edit: just to short circuit any "well, why aren't you running redundant regions" - we run redundant regions at all times. But for reasons of latency, many customers will bind to their closest region, and the nature of our technology is highly location-bound It is not possible for us to move active sessions to an alternate region. So something like this is... unpleasant.

Continue this thread — 4 replies

GrumpyNl8 replies#
How come they dont have power backups?
trelane1 reply#
Anything can fail, even your backup, and especially if it's mechanical.
rdines#
The battery backups (called uninterruptible power supplies) are only meant to bridge the gap between the power going out and the generator turning on, which is a few minutes. Did they say power was the issue this time? I suspect it’s actually something else (ahem network)
2-718-281-82814 replies#
is that just playing with words?

Continue this thread — 14 replies

thetinguy1 reply#
They do. I remember watching one of their sessions where they showed every rack having its own battery backup.
tyingq#
An article on that: https://datacenterfrontier.com/aws-designs-in-rack-micro-ups...

Interesting quote:
“This is exactly the sort of design that lets me sleep like a baby,” said DeSantis. “And indeed, this new design is getting even better availability” – better than “seven nines” or 99.99999 percent uptime, DeSantis said.

taf21 reply#
it was not a total power loss. out of 40 instances we had running at the time of the incident only 5 of our instances appeared to be lost to the power outage. the bigger issue for us was ec2 api to stop/start these instances appeared to be unavailable (but probably due to the rack these instances were in having no power). The other issue that was impactful to us was that many of the remaining running instances in the zone had intermittent connectivity out to the internet. Additionally, the incident was made worse by many of our supporting vendors being impacted as well...

IMO it was handled rather well and fast by AWS... not saying we shouldn't beat them up (for a discount) but being honest this wasn't that bad.

res0nat0r#
If the rack your instances are running in are totally offline then the ec2 api unfortunately can't talk to the dom0 and tell the instances to stop/start, so you get annoying "stuck instances", and really can't do anything until the rack is back online and able to respond to API calls unfortunately.
TrueDuality#
According to the SOC certifications they give their customers they do.
redm#
Some datacenter failures aren't related to redundancy. Some examples: 1) transfer switch failure where you can't switch over to backup generators and the UPS runs out, 2) someone accidentally hits the EOD, 3) maintenance work makes a mistake such as turning off the wrong circuits, 4) cooling doesn't switch over fully to backups and while your systems have power, its too hot to run. The list can go on and on.

I'm not sure why this is a big deal though, this is why Amazon has multiple AZ's. If your in one AZ, you take your chances.

Spooky23#
Their datacenter(s) aren’t magic because they are AWS. That facility is probably a decade old and like anything else as it ages the technical and maintenance debt makes management more challenging.
chousuke1 reply#
Sometimes, you have a component which fails in such a way that your redundancies can't really help.

I once had to prepare for a total blackout scenario in a datacenter because there was a fault in the power supply system that required bypassing major systems to fix. Had some mistake or fault happened during those critical moments, all power would've been lost.
Well-designed redundancy makes high-impact incidents less likely, but you're not immune to Murphy's law.

macintux1 reply#
To my mind, among the more frustrating aspects to implementing protection against failure is that the mechanisms to be added can themselves cause failure.

It's turtles all the way down.

Continue this thread — 1 reply

vinay_ys2 replies#
This is quite interesting as they claim their datacenter design does better than Uptime's Tier3+ design requirements which require redundant power supply paths. [https://aws.amazon.com/compliance/uptimeinstitute/]. I really hope they publish a thorough RCA for this incident.
tyingq4 replies#
"Electrical power systems are designed to be fully redundant so that in the event of a disruption, uninterruptible power supply units can be engaged for certain functions, while generators can provide backup power for the entire facility." https://aws.amazon.com/compliance/data-center/infrastructure...

So they have 2 different sources of power coming in. And generators. They do mention the UPS is only for "certain functions", so I guess it's not enough to handle full load while generators spin up if the 2 primaries go out. Or perhaps some failure in the source switching equipment (typically called a "static transfer switch").
Some detail on different approaches: https://www.donwil.com/wp-content/uploads/white-papers/Using...

vinay_ys1 reply#
Usually when someone claims T3+ they mean they have UPS clusters in 3+1 (or such) configuration and two different such UPS clusters power two power-strips in a rack. Then, would also have incoming grid power supply from two different HV sub-stations with non-intersecting cable paths. They would also have diesel power generators in 3+1 or 5+2 configurations with automatic startup time in seconds. The UPS's power storage (chemical or potential energy based devices) can hold enough energy to handle full load for several minutes. If these are design and maintained correctly, even while concurrent scheduled maintenance is ongoing, an unexpected component failure should not cause catastrophic outage. At each layer (grid incomers, generator incomers, UPS power incomers) there are switches to switch over whenever there's a need (maintenance or failure).

If they claim tier4, then they basically have everything in n+n configuration.

Continue this thread — 1 reply

dylan60411 replies#
The generators should be powering up as soon as one of the 2 different sources goes down. It takes generators a few minutes to power up and get "warmed up". If they don't start this process until both mains sources are down, then oops, there's power outage.

I used to work next door to a "major" cable TV station's broadcast location. They had multiple generators on-site, and one of them was running 24/7 (they rotated which one was hot). A major power outage hit, and there was a thunderous roar as all of the generators fired up. The channel never went off the air.

Continue this thread — 11 replies

rainbowzootsuit#
Likely the UPS can't run HVAC, and you are in an overheat condition in about two minutes with a fully loaded data center without cooling. Proportionately longer as load is reduced.

Continue this thread — 1 more reply

Continue this thread — 1 more reply

Continue this thread — 4 more replies